Rki-instruments GX-2001 Data Logging with Calibration Station Bedienungsanleitung Seite 46

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 57
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 45
46 • Calibratin
g
the Model GX-2001 with the Calibration Station
8. Connect the polyurethane tubing from the regulator to the
Span Gas In tting on the back of the GX-2001 Calibration
Station.
9. Make sure the Calibration In and Calibration Out tubing is
properly attached to the Calibration Adapter. This tubing was
connected at the factory.
Auto-Calibrating the Model GX-2001
1. Make sure you have properly setup the GX-2001 Calibration
Station following the instructions under “Preparing for
Calibration.
2. Turn on the computer, then launch the GX-2001 Data
Logging Software.
3. Check the Automatic Calibration box on the Download
window.
4. Using the On/Off switch, turn on the GX-2001 Calibration
Station.
5. Insert the Model GX-2001 into the Data Logging/Charger
Station on top of the GX-2001 Calibration Station.
Figure 28. Choosing the Automatic Calibration Option
Seitenansicht 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 56 57

Kommentare zu diesen Handbüchern

Keine Kommentare